Energy saving refrigeration solution supplier since 2004.                                                                                                                                                                                                                                                                                                   

Language

Cold water machine the capacity coefficient of performance requirements

2020/10/13
1. Piston/vortex type water industrial ice machine, the coefficient of performance ( COP) Requirements are as follows:
when the rated refrigerating capacity is less than 528 kw, the COP should not be less than 3. 8; When the rated refrigerating capacity 528 ~ 1163 kw, the COP should not be less than 4. 0; When the rated refrigerating capacity is more than 1163 kw, the COP should not be less than 4. 2;

2. For, the coefficient of performance ( COP) Requirements are as follows:
when the rated refrigerating capacity is less than 528 kw, the COP should not be less than 4. 10; When the rated refrigerating capacity 528 ~ 1163 kw, the COP should not be less than 4. 30; When the rated refrigerating capacity is more than 1163 kw, the COP should not be less than 4. 60;

3. For centrifugal chiller, the coefficient of performance ( COP) Requirements are as follows:
when the rated refrigerating capacity is less than 528 kw, the COP should not be less than 4. 40; When the rated refrigerating capacity 528 ~ 1163 kw, the COP should not be less than 4. 70; When the rated refrigerating capacity is more than 1163 kw, the COP should not be less than 5. 10;

4. For evaporative cooling or the wind cold water machine/piston/vortex type water industrial ice machine, the coefficient of performance ( COP) Requirements are as follows:
when the rated refrigerating capacity is less than or equal to 50 kw, the COP should not be less than 2. 40; When the rated refrigerating capacity greater than 50 kw, the COP should not be less than 2. 60;

5. For air-cooled or evaporative cooling screw water chillers, the coefficient of performance ( COP) Requirements are as follows:
when the rated refrigerating capacity is less than or equal to 50 kw, the COP should not be less than 2. 60; When the rated refrigerating capacity greater than 50 kw, the COP should not be less than 2. 80;

6. The integrated part load performance coefficient of water cooled screw chiller, IPLV) Requirements are as follows:
when the rated refrigerating capacity is less than 528 kw, the IPLV should not be less than 4. 47. When the rated refrigerating capacity 528 ~ 1163 kw, the IPLV should not be less than 4. 81; When the rated refrigerating capacity is more than 1163 kw, the IPLV should not be less than 5. 13;
If you have plenty of time, you can learn how to take care of ice maker machine. Also, invest in the right ice maker machine cold room supplier.
Guangzhou Icesource Co., Ltd works hard to enhance continuously our reputation for accessibility, professionalism, performance, and the depth and quality of our long-term consultative relationships with clients.
When you choose to buy instead of ice maker machine, the money you save may allow you to buy multiple other necessities, more than you had initially planned on buying.
While the productivity and efficiency benefits of automation are unequivocal for manufacturing cold room supplier, the need for skilled humans to operate, utilize and advance technologies is equally unmistakable.
CONTACT US
Just tell us your requirements, we can do more than you can imagine.
Send your inquiry

Send your inquiry

Choose a different language
العربية
English
Español
français
Polski
Português
русский
Türkçe
Current language:English